How much pipe do I need with the Lithotherm system?

Find out more about how we approach this building scenario.

It depends on what output you need from the system. To get the full output you will need 10m of pipe per sq.m of Lithotherm tile, with a maximum loop length of around 100m, remembering to add some for tails back to the manifold. Click here for the output chart for the system with different flow temps and different finishes.